1 USER MANUAL BNW - 50 Bridge Navigational Watch Alarm System Rev. M00-0481-01
10 2.2.2 VISUAL INDICATION If not “RESET” during this dormant period (3~12 minutes), visual indication will be initiated for the next 15 seco
11 CHAPTER 3 PRODUCT SPECIFICATION 3.1 DISPLAY UNIT (BNW-50) SCREEN SIZE ……………… 4.3 INCH TFT COLOR LCD, 480 X 272 PIXELS POWER CONSUM
12 3.4 ALARM UNIT (BNW-53) POWER CONSUMPTION ……………… max 30mA / unit (24V DC) SIZE ……………… 126x90x30 mm (H x W x D) WEIGHT
13 3.6 COMPONENTS 3.6.1 BNW-50 SPECIFICATION NO NAME MODEL NAME QUANT REMARK 1 Display unit desktop BNW-50 1 SET Bracket, protection c
14 CHAPTER 4 BNW-50 (DISPLAY UNIT) - Rated input voltage DC 24V (NOTE) Program version may change without notice for performance improve
15 System stops operating and goes into sleep mode by pressing this button and entering the password. In order to deactivate the
16 4.3 OPERATION SCREEN BNW-50’s current operational status appears on the screen. From menu, press ESC then will move to the operati
17 4.4.1 OPERATION SETUP You can change and save the Operational mode, the dormant period, the delay between the 2nd & 3rd stage al
18 Activated : The dormant period timer will be operated. Deactivated : The dormant period timer will not be operated. AC
19 The period of 1st stage bridge audible alarm Tone. You can change the Reset unit (BNW-52/52W)’s period of 1st stage bridge audible alar
20 ※ However, if setting by use the additional visual indication and 1st stage bridge audible alarm, The ALARM UNIT A and B will cha
21 Saving the VDR data by using the SD card (Record VDR data on SD card) After inserting the SD card, by using and , select the “ Record VDR dat
22 4.5.1 OPERATION SETUP You can change and save the Operational mode, the dormant period, the delay between the 2nd & 3rd stage al
23 4.5.2 SETUP ALARM UNITS On this menu, you may select the 2nd & 3rd stage remote audible alarm of the each processor unit’s interface termi
24 After changing the settings pressMENU, then you will be asked if you wish to save. Press " YES " then to
25 You must be aware that by using this function, all the settings will initialize. Self Testing - Refer to 4.4.2 SYSTE
26 4.6 OPERATIONAL DESCRIPTION As shown on the right, "Operational Mode = Manual ON, Dormant period = 3 minutes, the delay between the 2n
27 4.6.3 1ST STAGE BRIDGE AUDIBLE ALARM If not “RESET”, the BNW-50 will additionally sound a 1st stage bridge audible alarm on the bridge 15 secon
28 4.6.6 EMERGENCY CALL BNW-50 has built-in emergency call function. If the EMG button of display unit (BNW-50) is pressed
29 4.6.7 MALFUNCTION INDICATION BNW-50 provides indication to the following malfunction. If the malfunction is activated, the display
3 QUICK USER MANUAL NAME [MENU] [ENT] [CHECK] [EMG] [ESC] [RES] [POWER] [DIRECTION] BUTTON MENU EMG ESC RES 1. PASSWORD SETTING ① When
30 CHAPTER 5 BNW-51 (PROCESSOR UNIT) 5.1 LED FUNCTION (FRONT) Bridge Navigational Watch Alarm SystemProcessor UnitPOWER ALARMERRORAUTO TIMERB
31 5.2 POWER AND INTERFACE (BACK) DC FUSE(5A)FUSEINTERFACE110/220VACGND14FUSEAC FUSE(2A)28124VDC401327 1) AC Fuse (2A) : 2A is used as the
32 CHAPTER 6 INSTALLATION 6.1 POWER SUPPLY You should connect the Processor unit(BNW-51) to the Main power supply(AC 220V) using the AC cabl
33 6.2.1 BRACKET MOUNTING Before installing, consider the display unit’s weight and search for the most convenient place for you. Instal
34 audible alarm period can be changed from the setup menu. By using the jump pin (CN3: Tone OFF) from internal PCB, the 1st stage
35 6.6 2ND & 3RD STAGE REMOTE AUDIBLE ALARM (ALARM/A~G) Install the alarm unit (BNW-52) in the officer’s room or the captain’s roo
36 6.7 EXTERNAL FAILURE ALARM OUTPUT (ALARM/FAIL) Connect the failure alarm output to the external alarm. These two terminals are
37 6.10 NMEA INPUT (NMEA/RXD) You can connect the digital equipment which can output the NMEA data (reset, alert etc). Also, when digital
38 CHAPTER 7 INSTALLATION CONSIDERATION 7.1 GENERAL The following requirements are included in IMO resolution MSC.128(75) concerning the i
39 CHAPTER 8 MOTION SENSOR 8.1 OPERATING MOTION SENSOR We have adapted Doppler radar principle so the sensor can detect the microwave (MW) an
4 CAUTION 1. This BNWAS can be switched ON/OFF or settings can be changed with password, therefore only authorized person (captain) can change or s
40 3) Insert the adapter below the bracket
41 Check the operation after the installment Move around in the detective range after installation and check if the Green lamp (PIR), Brown lamp
42 CHAPTER 9 TEST AFTER INSTALLATION Go through the check list below after the installing the equipment. No. Check list OK 1 Turn on the BNW-5
43 CHAPTER 10 MAINTENANCE AND FAULT DIAGNOSIS 10.1 SYSTEM MAINTENANCE Constant maintenance is required to maintain the functionality of the equ
44 2 BNW-50 does not turn on Check the AC or DC fuse. Check the power of AC input (220V) and DC input (24V) Check the power cable’s connection. 3 R
45 CHAPTER 11 NMEA SENTENCE (IEC 61162-1) BNW-50 provides the interface such as IEC 61162-1 ALR, EVE…etc with the message below. SETTINGS : Bi
46 11.4 GLL – Geographic position This sentence is a primary source of position information for the transponder when connected to
47 CHAPTER 12 PACKING LIST 12.1 BNW-50 (STANDARD) BNW-50(Display Unit Desktop) NO. Item External Feature STANDARD Q’ty CHK Remark BNW-50 1 D
48 2A/250V[20mmX5mm] 7 FUSE CODE NO. 527-2002-1Q 2 AC POWER 5A/250V[20mmX5mm] 8 FUSE CODE NO. 527-2005-1Q 2 DC Power 12.3 BNW-52 FLUSH
49 12.6 BNW-52W WATERTIGHT TYPE (STANDARD) 12.7 BNW-52 DESK TYPE (OPTION) BNW-52(Reset unit desktop) NO. Item External Feature STANDARD Q’ty
5 ---- CONTENTS ---- CHAPTER 1 ABOUT BNWAS ...
50 BNW-B(Desk type bracket) BNW-B 2 Bracket CODE NO. E02-1811-01 1 BNW-B-A(Desk type bracket installation accessory) M3X6 STS304 3 Bolt COD
51 CHAPTER 13 DIAGRAMS 13.1 INTERCONNECTION DIAGRAM Ext Alarm1 PORTWatertightProcessor UnitDisplay UnitMotion SensorINTERCONNECTION DIAGRAMmax.
52 13.2 INSTALLATION DIAGRAM ( EXAMPLE-1 ) 1SLDDISPLAYIN/OUT2 3 4TXD24VRXD212024VGNDALARME191824VGNDALARMD171624VGNDALARMC151424VGNDALARMB3130INP
53 13.3 INSTALLATION DIAGRAM ( EXAMPLE-2 ) : Z8-2M-05A CABLE ASS'Y.: 6p shield(>UL2464-6C-24AWG): 2p shield(>UL2464-2C-20AWG): 3p shiel
54 13.4 INSTALLATION DIAGRAM ( EXAMPLE-3 ) 1SLDDISPLAYIN/OUT2 3 4TXD24VRXD212024VGNDALARME191824VGNDALARMD171624VGNDALARMC151424VGNDALARMB7612VRE
55 13.5 BNW-50 OUTLINE DRAWING 12AB345 6CDEMENUESCEMG RES7 8 967134258
56 13.6 BNW-51 OUTLINE DRAWING 220±1210±1198±1ALARMCBridge Navigational Watch Alarm SystemA1BCAUTOPOWER ERROR ALARM TIMERProcessor UnitBNW-5123 4
57 13.7 BNW-52 FLUSH TYPE OUTLINE DRAWING BNW-52Reset unitA123 4 5 6 7 8 9BC108SAMYUNGResetto resetPush button126±1105.5ED29.7±126.24-Ø3.390±17666
58 13.8 BNW-53 FLUSH TYPE OUTLINE DRAWING 12A345 6BCSAMYUNGto bridgeAssistanceAlarm unitBNW-53108126±17 8 990±176664-Ø3.3ED105.529 7±126 2
59 13.9 BNW-52W WATERTIGHT TYPE OUTLINE DRAWING to resetAB1 2SAMYUNG3 4Push buttonResetReset unitBNW-525 6127±1178±17 8 9CDE22±1175±192.5±1
6 4.6 OPERATIONAL DESCRIPTION ...
60 13.10 BNW-B FLUSH TYPE OUTLINE DRAWING (BNW-52,53) 66±11 2A3 4 5 6BC4-M3TAP4-Ø3,5Ø3554±17 8 976.6±190±1ED90±1108.2±1114±11.2±0.138±113±1
61 13.11 MOTION SENSOR(DND-300M) OUTLINE DRAWING 1 32 4ABCDE122.8±15 6 7 8 958±1 79±1
62 CHAPTER 14 WARRANTY INFORMATION Thank you for purchasing SAMYUNG ENC LTD’s BNW-50. This manual includes the proper way of operat
7 CHAPTER 10 MAINTENANCE AND FAULT DIAGNOSIS...43 10.1 SYSTEM MAIN
8 CHAPTER 1 ABOUT BNWAS The purpose of a bridge navigational watch alarm system is to monitor the bridge activity and detect operator disability
9 CHAPTER 2 OPERATION OF BNWAS This BNW-50’s setting is only adjustable by using password, therefore only authorized person (captain)